Why Do Aquatherm Pipes Fail?

Domestic water supply applications of Polypropylene (PPR) have been commercialized largely under the Aquatherm trade name and manufactured in Germany.  After a period of reportedly reliable performance in Europe, Aquatherm began to market the product in Australia, Canada, the US, and elsewhere.  Recently a string failures started to appear; first in Australia and now increasingly in the US. 

After fire, water damage is the most expensive peril that a building owner may face.  Many of these are winding up in the courts in what looks like the three-way shoot out at the end of the Clint Eastwood movie, The Good, The Bad, and The Ugly.  The contractor is pointing at the manufacturer who in turn is pointing back at the owner/operator who is pointing alternately at the contractor and the manufacturer. 

For the record, I like PPR for many reasons, but there appears to be 3 main vulnerabilities with PPR: the manner in which it is clamped, the temperature of the water, and the water chemistry – specifically the presence of copper ions.  I call it the witches brew. If all three vulnerabilities are present, then the likelihood of failure is very high. If only one (or maybe two) of the vulnerabilities are present, the likelihood of failure seems substantially lower. 

The problem is that each of the litigating parties may be responsible for at least one of the vulnerable conditions. Therefore, it is tremendously difficult to assign a percentage of the blame on any single party especially where the absence of any one condition may result in no failure.

Aquatherm had claimed that standard pipe clamps could be used with loosely specified modifications.  In practice the pipes are sized in the Metric system and the clamps were sized in the Imperial measurement system.  Further, the materiel is soft so there was little feedback for the mechanics accustomed to using a torque wrench.  Often we’ll find the failed piece deformed inside the clamp.  Is the contractor to blame or Aquatherm?

In another case, Aquatherm specified strict temperature and pressure limitations.  In the real world, we found two boilers set up incorrectly causing occasional fluctuations beyond the temperature limits – normally not a problem with most other piping systems.

In another case, the boilers had CuNi (Copper/Nickel) heat exchangers that, if not correctly installed or maintained, may be a source of copper ionization.   How is the owner / HVAC contractor to know about these details?

One of the advantages of Aquatherm is that it can be run at a much faster flow speed than other pipes.  If you run water too fast in a system mixed with copper, the turbulence can erode the copper releasing ions to the water system, which can then attack the Aquatherm.  Most of the retrofits will have mixed systems in one form or another.  Whose responsibility is it to manage mixed systems?

I have been contacted by attorneys on both sides of more than one PPR lawsuit. Most lawyers are looking for a sharp knife to cut their client free from culpability.  When I share my thoughts on the topic, based on real-life experience, I’m rarely called back. The last thing they want to hear is that there is plenty of blame to go around. I believe that an inherent bias is baked-in, leading to closed settlements.  

So, Why DO Aquatherm Pipes Fail?

The answer is simple.  Information needs to flow to the industry without fear of repercussion so that owners and operators and installers can mitigate the risk.  Most piping materials seem to go through a period of failures until the industry can see how they actually perform over the long term. PolyButylene, CPVC, and PEX have all had their time in the hot-seat.  Polypropylene, in my opinion, holds great promise in some applications.  Few people want to talk about the details and court settlements are often sealed, so the public and the industry are uninformed. 

Instead of learning from mistakes, a new game plays out anew for every instance of failure.  This is counterproductive. What really needs to happen is that each of the parties need to fess up, mitigate the failures, and then share information with everyone else so that the problems can be ironed out as soon as possible and this innovative material can achieve its potential.

 

Case Study: Harrison West Tower Re-pipe

Introduction

The Harrison West Condominium Association required a re-pipe of their historic 24-floor residential tower situated in the desirable PSU area of Portland Oregon. Community Engineering Services, PLLC formed a team with engineering specialists Dan Robles, PE,  David Coles, PE, Architect Richard Bosch, AIA and a CM consultant.  Through the client’s commitment to research, analysis, and insisting upon the services of  experienced Engineers and Architects, many unique opportunities were discovered while substantial costs and risks were avoided.  The resulting renovation is now considered among the most robust in the Pacific Northwest. 

Case Study: Harrison West Tower Re-pipe

Step 1: Piping Condition Assessment

The purpose of the piping condition assessment was to determine without doubt, the actual condition of the existing piping system.  This knowledge would drive many decisions such as schedule, material, priorities, proposals, and techniques that could or could not be used when performing the repipe.  A typical Coengineers piping condition assessment may be referenced here (Assessment report)

Step 2: Material Selection Process

The HOA board was especially concerned about various piping materials and requested a review of Epoxy Liner, Copper, and various plastic products.  Epoxy was rejected (Epoxy Report), Copper was compared alternates such as PEX and Polypropylene (Tech Study Report)

Step 3: Contractor RFI/RFP process

RFI process sought to find the most qualified mechanical services  firms who would be willing to undertake such a project.  For each, we requested a rough estimate for performing the job in each of three materials; Copper, Copper/PEX, and Polypropylene. The Board selected Polypropylene. The RFI approached a dozen qualified firms in the Portland Area. 

Step 4: Contractor RFP process

Of the five top candidates from the RFI process, three were selected for the RFP process. Polypropylene (PP-R) was somewhat unfamiliar for many contractors and represented many unknowns.  Ultimately, the board selected McKinstry, Inc due to their excellent reputation and prior experience in PP-R.  The polypropylene piping material and complete plumbing system was supplied by Aquatherm.  

Step 5: Detailed Statement of Work  

As the RFP prices and ideas came in, it was obvious that a different approach to re-piping the building was needed – it would not be possible to rely on the plumbers  for a solution. We consulted with Duane Tilden, P. Eng., a member of the Coengineers network, who has re-piped over 40 structures of this type.  His recommendation, based on a similar re-pipe he had performed in Canada, was to send the main risers up through the refuse disposal closet   This suggestion was a perfect fit for the Harrison West Project and ultimately defined the strategy for this re-pipe.  

Step 6: Re-piping The Harrison West.   

Steps HW Re-Pipe

Renderings by Richard Bosch Architecture, Portland OR

plan schematic

Plan Schematic (click to enlarge) c. Richard Bosch, AIA

Conclusion;

The Harrison West Condominium Association received a ultra-clean, high reliability potable water system using non-metallic components covered by an unprecedented 10-year warranty and $15M manufacturers insurance policy.  This project is unique in many important technical areas and will long be considered a landmark re-pipe in the engineering profession.  The price of the project is scheduled to compete with copper while the carbon footprint (over copper mining, smelting, transportation, and recycling) is dramatically lower.  This unique high-profile re-pipe will have a direct and positive impact on home values for this community.